I commissioned the heat exchanger. The air comes from outside in pipes buried underground. This heats the air to about 12C. This is then heated by the exhaust air in the heat exchanger giving us heated, fresh air. However it wasn't working correctly and the input air was about 25% of what it should be along with the fact that the air seemed to be really humid. The only thing that seemed to like the situation was Olga's orchids which were thriving.
I had to dig a hole outside to uncover the air pipes and see what the problem was.

I found that the pipes were not connected very well and they allowed water into the system.

Then looking at the manifold, I found that they
had left the blanking plates in (which stops air getting in) Doh!
This explained the low air intake volume.

I then had a look in the air box and found about 5 gallons (25Lt) of water - this explained the humidity. Double Doh!

Now I had found the problem, I sealed the unit properly and got the builder to make an inspection hole around the pipes instead of burying them.


Now the system is working perfectly and the air is
completely dry.
Sadly Olga's orchids are not doing so well anymore.